Home Products Services About Us Contact Us




 Airflow Transducer Model 6332 / 6332D
 
Specification Sheet (PDF 139K)









Product Line Quality Control
Quality Control monitoring and controlling
air velocity and distribution during drying/
shaping process.

PCB Temperature monitoring
Combined with thermographic system
measure air velocity across the board
to evaluate the cooling efficiency.
(Photo provided by NEC San-ei Instruments, Ltd.)



Air Velocity Monitor for Local Exhaust
Ventilation and FFU (Fan Filter Unit)

Prevent exposure of hazardous materials to workers and prevent leakage by thorough monitoring and control of chamber airflow.

Residential Air Ventilation Monitoring
Ensure ventilation system efficiency by
actively monitoring system balance and
controlling airflow.


Features
  • 10 interchangeable probe options
  • Probes quickly and easily attach/detach
  • Digital Display Option (model 6332D)
  • Selectable Output (Output can be set to either voltage (0 to 5V) or current (4 to 20mA))

Specifications
 Model
6332 / 6332D
 Measuring Object

Clean air and compatible, non-combustible gases

 Measuring Range

Maximum range 0.1 ~ 50 m/s  (Range dependant on probe type*)

 Temperature Compensation Range

0.1-4.99 m/s
5.00-9.99 m/s
10.0-24.9 m/s
25.0-50.0 m/s
5~40°C
±0.25 m/s
±0.50 m/s
±1.25 m/s
±2.50 m/s
40~80°C
±0.35 m/s
±0.70 m/s
±1.75 m/s
±3.50 m/s
 Selectable Output Optio
(Set via onboard DIPswitch).

Current output: DC 4~20mA (Max. load resistance: 250Ω)

Voltage output: DC 0~5V

 Selectable Range Option

0~2, 0~5, 0~10, 0~25, or 0~50 m/s

 Display Resolution
(Model 6332D only)

Velocity Range: 0~2, 0~5, 0~10 m/s  →  Display Resolution: 0.01m/s
Velocity Range: 0~25, 0~50 m/s   →   Display Resolution: 0.1m/s

Power Supply

DC 12~24V

Power Consumption (Reference Value)

Approx. 2.0W (Under the following conditions - power supply: 12V, air velocity: approx. 10m/s, using a unit with a display with probe model 0965-03.) 

Power consumption rate is subject to change according to conditions such as air velocity, probe type and use of display.

Connection Wire Size

0.5 ~ 1.5 mm2

Operating Temperature Range

5 ~ 40°C

Storage

Temperature Range

-10 ~ 50°C

Dimensions   

Approx. 128(W)×78(D)×30(H) mm

Weight

Approx. 320g (11oz.)

Standard Accessory

Operation Manual : 1,  Main Unit Case: 1

Optional Accessory

Probe Cable (10m, 20m, 30m), Display Unit (Supplied with a case with a display window and 2 installation screws.), Dedicated AC Adapter (DC12V)


Model 0962-00
Caramel
Model 0963-00
Rod
Model 0964-01 Omni-direct Model 0965-00
Spherical



Model 0965-03/04
Caramel
Model 0965-03
Model 0965-04
Model 0965-07/08
Caramel




Probe Specifications
Model
Measuring Range
Sensor Type
0962-00, 0963-00 0.1~50.0m/s Uni-directional
0964-01, 0964-02 Omni-directional (Needle)
0965-00, 0965-01 0.1~25.0m/s Omni-directional (Spherical)
0965-03, 0965-04 0.1~25.0m/s

Mini-temperature-compensation-sensor integrated type

Omni-directional (Spherical)

0965-07, 0965-08

Mini-temperature-compensation-sensor independent type

Omni-directional (Spherical)


 


KANOMAX USA Copyright © 2011 KANOMAX USA, INC. All Rights Reserved.
219 US Hwy. 206, PO Box 372, Andover, NJ 07821
Tel: (973) 786-6386 / Fax: (973) 786-7586 / info@kanomax-usa.com